CIRCUTOR PowerStudio SCADA WAVE Authentication Bypass (CVE-2026-120387)

CVE-2026-120387 is an authentication bypass in CIRCUTOR PowerStudio SCADA WAVE for Windows.

Reviewed by
Brandefense Analyst Team
Published
Reading Time
3 min read
CVE ID
CVE-2026-120387
Vendor
CIRCUTOR
Affected Product
PowerStudio SCADA WAVE (Windows, 64 bit)
Exploitation
Not confirmed
Published
2026-11-17

CIRCUTOR says its shared JWT validation component accepts an unsigned token without verifying a cryptographic signature. A remote attacker who can reach an affected service could impersonate a user and access protected functions with that user's privileges.The CIRCUTOR record describes an improper verification of cryptographic signature (CWE-347), not direct code execution. The researcher's separate analysis says the bypass can enable another vulnerability chain, but the two findings must be assessed separately. Teams can use a vulnerability intelligence platform to track the affected build, correction owner, and verification date.

What it allows

How Does CVE-2026-120387 Bypass Authentication?

According to CIRCUTOR, the shared token-validation component accepts an unsigned JWT without checking its signature. A person without credentials could then present an identity claim and reach protected functions as another user. The researcher's analysis places the failure in a shared authentication library used across PowerStudio microservices.

Network reachability still matters: the researcher says service exposure differs by deployment and by service. Identify which affected services can be reached from untrusted networks or less trusted segments. This flaw gives access to functions with the impersonated user's privileges; it does not itself establish host-level code execution.

What Is Known About Exploitation?

Brandefense Blackhole counted three dark-chat posts mentioning CVE-2026-120387 from 19 August through 17 November 2026. The measured unit is posts, not distinct incidents, affected systems, or verified exploitation. Treat the discussion as a reason to review exposure and remediation promptly.

The CISA KEV catalog snapshot dated 13 November 2026 does not list this CVE. That snapshot predates the CNA publication and is only a dated catalog fact. It does not resolve whether any particular PowerStudio deployment has been attacked.

Who is affected

Which PowerStudio SCADA WAVE Versions Are Affected?

CIRCUTOR identifies the Windows 64-bit desktop product from version 24.8.0 up to, but excluding, 24.11.17.0. Its CNA record marks 24.11.17.0 unaffected and recommends updating to that version or later. The researcher assessed version 24.11.6.0; that tested build does not narrow the CNA's affected range.

Inventory installed PowerStudio SCADA WAVE builds and record the Windows host, running version, and reachable services. Apply the vendor update to affected systems, giving earlier attention to reachable services. For the vulnerability management workflow, assign an owner and a maintenance window before closing each finding.

What Should Defenders Verify After Updating?

After maintenance, confirm that the running PowerStudio SCADA WAVE version is 24.11.17.0 or later. Check each installed Windows instance rather than assuming a downloaded installer changed the active service. As a Brandefense precaution, review authentication and protected-function logs for unexplained identity or privilege use.

Such log events are investigation leads, not proof of this specific bypass. If the update cannot be applied immediately, restrict access to affected services from untrusted networks as an interim measure. Record that exception and recheck it through the patch management process.

Timeline

  1. 2026-08-02

    The researcher's public feed dates its JWT identity-forgery analysis to 2 August 2026; the article labels the discovery date as 21 July 2026.

  2. 2026-11-17

    CIRCUTOR published its CNA record for CVE-2026-120387, identifying affected and unaffected Windows versions and a CVSS 4.0 score.

What to do

  1. Inventory Windows installations

    Locate PowerStudio SCADA WAVE Windows 64-bit desktop installations. Record running versions and which services are reachable across network boundaries.

  2. Update affected versions

    Update installations from 24.8.0 up to, but excluding, 24.11.17.0. Follow CIRCUTOR's recommendation to install 24.11.17.0 or later.

  3. Verify the running build

    After maintenance, confirm each installed instance is running version 24.11.17.0 or later. Record the version and verification date.

  4. Review access while patching

    Restrict affected service access from untrusted networks until updated. Review authentication and protected-function activity for unexplained identity or privilege use.

What Brandefense can do

Frequently Asked Questions

Can CVE-2026-120387 be used without credentials?

Yes. CIRCUTOR describes a remote, unauthenticated authentication bypass when the attacker can reach an affected service.

Which PowerStudio version fixes CVE-2026-120387?

CIRCUTOR recommends version 24.11.17.0 or later. Its CNA record marks that version unaffected for the Windows 64-bit desktop product.

Does this flaw itself execute code?

No direct code-execution effect is stated for this flaw. The researcher describes it as an identity-forgery primitive that can support a separate vulnerability chain.

Why are there two CVSS scores?

CIRCUTOR uses CVSS 4.0 and assigns 10.0 Critical. The researcher's August analysis uses CVSS 3.1 and assigns 8.6 High; the scoring versions differ.

Sources

  1. CVE-2026-120387 RecordCIRCUTOR CNA
  2. PowerStudio JWT Identity Forgery Analysis0day Rubbish Research Team
  3. Known Exploited Vulnerabilities CatalogCISA
ShareLinkedInX
Brandefense logo

Stay Ahead of Digital Threats.

Take control of your digital security with an exclusive demo of our AI-driven threat intelligence platform.

Open The Full Demo Form →