Exposure requires Industrial OS with Node-RED installed and a version earlier than 4.3.4-1. Successful exploitation can cause remote code execution.Siemens assigns CVSS 3.1 and CVSS 4.0 scores of 10.0. The advisory classifies the weakness as CWE-306, Missing Authentication for Critical Function. Apply the fixed version through the organization’s patch management process.
What it allows
How Does CVE-2026-58115 Lead to Code Execution?
The affected Node-RED HTTP interface does not enforce authentication. A remote attacker can therefore reach programming nodes that can execute system commands on the server.
Siemens says an attacker could create malicious flows through that interface. Successful exploitation could execute arbitrary code on the underlying server with maximum privileges.
Who is affected
Four SIMATIC IoT2050 models are affected under the same software conditions. Each must run Industrial OS with Node-RED installed and a version earlier than 4.3.4-1.
| Product | Order number | Affected versions | Remediation |
|---|---|---|---|
| SIMATIC IoT2050 Advanced | 6ES7647-0BA00-1YA2 | All versions before 4.3.4-1 | Update to 4.3.4-1 or later |
| SIMATIC IoT2050 Basic | 6ES7647-0BA00-0YA2 | All versions before 4.3.4-1 | Update to 4.3.4-1 or later |
| SIMATIC IoT2050 M.2 | 6ES7647-0BB00-1YA2 | All versions before 4.3.4-1 | Update to 4.3.4-1 or later |
| SIMATIC IoT2050 SM | 6ES7647-0CA00-1AA2 | All versions before 4.3.4-1 | Update to 4.3.4-1 or later |
Siemens originally disclosed the Advanced model and released the fix on August 11, 2026. Its November 4 review added Basic, M.2, and SM under the same remediation.
What to do
-
Update to Industrial OS 4.3.4-1 or later
Apply the Siemens update to every affected model. Confirm both the device model and running Industrial OS version after deployment.
-
Remove Node-RED where it is not required
Siemens lists uninstalling Node-RED as a mitigation. This removes the vulnerable component where operational needs do not require it.
-
Harden Node-RED and restrict device access
Siemens recommends hardening Node-RED and protecting network access with appropriate controls. Use these mitigations while scheduling the update, not as a replacement for it.
-
Review unexpected Node-RED flow changes
Brandefense recommends checking for unapproved flow creation or modification on exposed devices. Investigate unexpected changes and preserve relevant device and network logs.
What Brandefense can do
- Watch your stack for exploited flaws
Name the vendors and products you run, and Brandefense alerts you when a CVE in them is exploited.
- See CVE-2026-58115 in Brandefense Atlas
The Atlas record of CVE-2026-58115: severity, exploitation status and the sources behind it.
- Vulnerability intelligence platform
Brandefense Vulnerability Intelligence follows which vulnerabilities attackers are using, so your team can patch what is under attack first.
Frequently Asked Questions
What is CVE-2026-58115?
It is a missing authentication flaw in the Node-RED HTTP interface on affected SIMATIC IoT2050 devices. It can allow unauthenticated remote code execution with maximum privileges.
Which SIMATIC IoT2050 models are affected?
Advanced, Basic, M.2, and SM models are affected when they run Industrial OS with Node-RED installed before version 4.3.4-1.
What fixes CVE-2026-58115?
Siemens recommends updating affected devices to version 4.3.4-1 or later. It also lists uninstalling or hardening Node-RED as mitigations.
Has CVE-2026-58115 been exploited?
Siemens says it is aware of published research about exploitation targeting VulnCheck's vulnerable Node-RED canary instances. The statement does not describe exploitation of customer deployments.
Sources
- Siemens ProductCERT Advisory SSA-834709cert-portal.siemens.com
- Siemens ProductCERT: Missing Authentication Vulnerability in Node-REDproductcert.siemens.com
- NVD: CVE-2026-58115NIST NVD