Skip to content
NewCybercrime Report 2026 · Eight Chapters · A Post Is Not An Incident → Explore The ChaptersCybercrime Report 2026 → Explore

WAGO WBM Routing Command Injection (CVE-2026-80466)

CVE-2026-80466 is a command injection vulnerability in WAGO Web-Based Management (WBM) routing configuration.

Reviewed by
Brandefense Analyst Team
Published
Reading Time
3 min read
CVE ID
CVE-2026-80466
Vendor
WAGO GmbH & Co. KG
Affected Product
WAGO CC100, PFC100 G2, PFC200 G2, TP600, Edge Controller and WP400 WBM
Exploitation
Not confirmed
Published
2026-11-23

CERT@VDE says an authenticated, low-privileged remote user can inject shell commands into routing parameters and potentially run commands with root privileges.The advisory was published on 23 November 2026 and covers several WAGO controller families running affected WAGO OS Linux firmware. This profile separates the routing flaw from CVE-2026-88850, a PROFIBUS authorization issue disclosed in the same advisory.

What it allows

How Does CVE-2026-80466 Cross the Privilege Boundary?

CERT@VDE describes insufficient validation of routing parameters in WBM. The supplied values are stored in a configuration file and later processed by a helper script running as root. This carries lower-trust management input into a privileged execution path.

The described attacker needs a low-privileged account and remote access to WBM. The advisory says successful exploitation may allow commands to run with root privileges. This is a potential consequence of the routing flaw, not a claim that every reachable controller has been compromised.

Brandefense Blackhole counted one dark-chat item mentioning CVE-2026-80466 between 25 August and 23 November 2026. The measured unit is an item mentioning the identifier, not an affected device or verified incident. This observation does not establish active exploitation.

As a defensive review derived from the vendor's attack path, check WBM routing changes made by low-privileged accounts. Correlate unexpected configuration changes with any available privileged-helper activity and management access logs. CERT@VDE does not provide a detection signature or a confirmed attack timeline.

Separate the sibling issue during triage: CVE-2026-88850 concerns missing authorization for protected PROFIBUS settings. CERT@VDE says low-privileged users may modify device addressing and SSA settings. Its CVSS 3.1 score is 8.1, and it is not the root command execution issue described here.

Who is affected

Which WAGO Firmware Is Affected by CVE-2026-80466?

CERT@VDE lists CC100, PFC100 G2, PFC200 G2, TP600, Edge Controller and WP400 devices. Its table covers model families 0750-811x, 0750-821x, 0751-9x01, 0752-8303-8000-0002, and the listed 0762-340x, 420x, 430x, 520x, 530x, 620x and 630x variants. Match the exact model identifier against the vendor table before changing firmware.

The vendor marks standard wago_os_linux below 4.10.0 (FW32) and custom wago_os_linux below 4.10.0 (70) as affected. It recommends updating standard firmware to 4.10.0 (FW32) or higher. For the latest custom firmware, the advisory directs customers to WAGO support.

Record the model, installed firmware track and running version in the patch management record. A custom build needs confirmation from WAGO support before selecting the replacement image. Verify the running version after the device is updated.

Use vulnerability prioritization to put reachable WBM interfaces and low-privileged accounts first in the review queue. The Vulnerability Intelligence product page describes how to organize affected assets and remediation decisions.

Timeline

  1. 2026-11-23

    CERT@VDE published VDE-2026-096 with the affected model table and standard firmware fix.

What to do

  1. Inventory affected models and management access

    Match each device model against CERT@VDE's affected-product table. Record whether its WBM interface is reachable and which low-privileged accounts can use it.

  2. Update standard firmware

    Update affected standard WAGO OS Linux firmware to 4.10.0 (FW32) or higher, following WAGO's device-specific release guidance.

  3. Confirm the custom firmware path

    For a custom firmware build, ask WAGO support for the latest applicable image. Do not assume the standard FW32 image applies to the custom track.

  4. Verify the running version

    After the update, read the version from the running device. Confirm standard firmware is 4.10.0 (FW32) or later, or confirm the support-approved custom release.

  5. Review management activity

    Review WBM routing changes made by low-privileged accounts and correlate them with available management and privileged-helper logs. This is our defensive review step, not a vendor detection rule.

What Brandefense can do

Frequently Asked Questions

Does CVE-2026-80466 require authentication?

Yes. CERT@VDE describes an authenticated, low-privileged remote user with access to WBM routing configuration.

Why can a routing change lead to root commands?

CERT@VDE says routing values are stored in a configuration file and later processed by a privileged root helper script. Insufficient input validation creates the injection path.

What version fixes standard WAGO OS Linux firmware?

CERT@VDE recommends firmware 4.10.0 (FW32) or higher. For custom firmware, it instructs customers to contact WAGO support for the latest build.

Is the PROFIBUS issue the same flaw?

No. CVE-2026-88850 is a separate missing-authorization flaw affecting protected PROFIBUS configuration. The routing command injection is CVE-2026-80466.

Sources

  1. WAGO: Improper Authorization and Privilege EscalationCERT@VDE
  2. CVE-2026-80466 RecordNIST NVD