Glossary term
Critical infrastructure
Critical infrastructure means the systems and assets, physical or virtual, that are so vital that losing them would seriously harm security, the economy, or public health and safety.
Quick links
Press Enter to search, Esc to close
Significant cyber incident
On 17 December 2016, malware called Industroyer, also known as CrashOverride, disrupted a transmission substation outside Kyiv, Ukraine.
In short
On 17 December 2016, malware called Industroyer, also known as CrashOverride, disrupted a transmission substation outside Kyiv, Ukraine. A US Department of Energy laboratory report says the grid operator Ukrenergo lost control of the substation and power was out for over an hour in Kyiv city and region. The malware could send commands in substation protocols and wipe files. US and MITRE sources attribute it to Russia's GRU unit Sandworm.
Just before midnight on 17 December 2016, attackers launched Industroyer against the Pivnichna transmission substation outside Kyiv, according to a US Department of Energy laboratory report. By midnight, Ukrenergo had lost control of the targeted substation. Power was out for over an hour in the city of Kyiv and the Kyiv region. A US indictment says the supply of electricity to Kiev was disrupted for approximately one hour.
The malware was built to take control of substation switches and circuit breakers. It also had a wiper that deleted key system files, and a part aimed at Siemens protective relays. The laboratory report says the wiper made operators lose control over and view of the ICS environment.
The attackers had been inside for months. The laboratory report gives about 3 February 2016 as the likely first access, after spearphishing against electric power organizations. The US indictment says the network had been compromised since around April 2016. Sources differ on this date.
The malware was made public in June 2017. CISA issued alert TA17-163A on 12 June 2017. On 20 July 2021 CISA added that the US Government attributes the activity to Russian nation-state cyber actors. Ukrainian government pages could not be opened for this profile, so the account here rests on US and UK official sources and MITRE ATT&CK.
Per the US indictment, the conspirators deploy destructive malware against companies supporting Ukraine's power grid. This is the earlier attack.
The US Department of Energy laboratory report gives this as the likely first access to Ukrenergo enterprise networks (sources differ; the indictment says around April 2016).
The US indictment says the transmission company's network has been compromised since about now.
The laboratory report says the attackers begin capturing credentials.
Per the US indictment, destructive malware hits Ukraine's Ministry of Finance and State Treasury Service in a separate attack.
The attackers deploy and launch Industroyer at the Pivnichna substation.
Ukrenergo has lost control of a targeted substation; Kyiv city and region lose power.
Power is restored. The laboratory report says the entire outage lasted just over an hour.
CISA publishes alert TA17-163A on CrashOverride malware.
The US indicts six GRU Unit 74455 officers, including over the 2015 and 2016 attacks on Ukrainian electrical companies (MITRE ATT&CK).
On 20 July CISA updates the alert to say the US Government attributes the activity to Russian nation-state cyber actors.
A US advisory (AA22-110A, last revised 9 May 2022) says GTsST actors ran the 2016 intrusion campaign against a Ukrainian transmission company.
The laboratory report says the attackers likely got in through spearphishing with a malicious Office attachment that contained macros. They then used captured credentials to reach the Pivnichna substation environment through a device connected to both the IT and ICS networks. MITRE ATT&CK lists the steps it ties to this campaign: a script that tried RPC authentication against many hosts, Mimikatz to capture legitimate credentials, two created accounts named “admin” and “система” (System), valid accounts used over VPN connections and dual-homed systems, and MS-SQL access to a pivot machine that gave code execution across the ICS network. The attackers also disabled event logging on compromised systems.
Industroyer is a modular framework. The laboratory report says each impact module is tailored to one ICS protocol used in the power sector and is loaded through a custom launcher. CISA says the reported modules focus on IEC101, IEC104 and IEC61850. The UK NCSC adds OPC DA and IEC60870-5-104. MITRE ATT&CK says the malware toggles breakers to the open state using unauthorized command messages. A trojanized Windows Notepad gave extra persistence, and Tor nodes were used for command and control.
The wiper deleted configuration and system files to slow recovery of the SCADA systems and left operators without control or view. The laboratory report says it came with an attempted denial-of-service attack on four Siemens SIPROTEC protective relays. MITRE ATT&CK says that tool uses CVE-2015-5374. CISA notes that such a relay would need a manual reset.
CISA says the malware is second stage and can run without its first command channel, so ordinary detection may miss it before it runs. It abuses the lack of authentication in common ICS protocols to issue commands that field devices accept.
Who attributed it, and how firm it is
CISA, 20 July 2021 (update to alert TA17-163A): the US Government attributes the activity to Russian nation-state cyber actors, who deployed the malware in a cyberattack against Ukrainian critical infrastructure.
US advisory AA22-110A (last revised 9 May 2022): says activity "previously attributed to GTsST by the U.S. Government and the UK Government" includes a 2016 intrusion campaign against a Ukrainian electrical transmission company where CrashOverride (Industroyer) was deployed. It calls GTsST also Unit 74455.
MITRE ATT&CK: describes the 2016 Ukraine Electric Power Attack as a Sandworm Team campaign and says Sandworm Team has been attributed to Russia's GRU Main Center for Special Technologies, military unit 74455.
US indictment, October 2020 (Western District of Pennsylvania): says six GRU officers working for Military Unit 74455, known to researchers as Sandworm Team, conspired to deploy destructive malware, and says the conspirators carried out the 17 December 2016 intrusion. These are charges, not court findings.
Sources differ on the type of substation: MITRE ATT&CK says distribution substations; the indictment, the laboratory report and the UK NCSC say transmission. The two dates for first access also differ (February vs April 2016).
The UK NCSC page opened does not itself attribute the 2016 attack. Ukrainian government attribution statements could not be opened.
Power was out for over an hour in the city of Kyiv and the Kyiv region, per the US Department of Energy laboratory report. The US indictment says the supply of electricity to Kiev was disrupted for approximately one hour. The laboratory report says the entire outage lasted just over an hour and affected a single transmission level substation.
The wiper deleted key system files and configuration files, which cost operators control over and view of the ICS environment and slowed recovery.
No figure for customers or megawatts affected was found in an opened official source, so none is given.
CISA said in 2017 it knew of no evidence that the malware had affected US critical infrastructure.
The attackers reached the substation environment through a device connected to both IT and ICS networks. A dual-homed host is a bridge for an intruder.
CISA says the malware exploits the lack of authentication in common ICS protocols. Where old equipment cannot check commands, use ICS firewalls or upgrade the field devices.
The attackers used captured credentials and valid accounts over VPN. CISA advises multi-factor authentication, least privilege and separate credentials for corporate and control networks.
The laboratory report puts first access months before the outage. It assesses that observables from the steps could have been noticed earlier.
The wiper deleted configuration files. CISA advises backups of configurations and a tested restoration plan with gold images.
CISA says the malware can run without its first command channel, so defenders should use behavior-based detection of activity that comes before it.
List every machine with a network connection to both corporate IT and the control network. Remove or tightly lock down each one.
Confirm that control network accounts are separate from corporate accounts, use multi-factor authentication, and are not shared through one directory.
Review VPN and vendor access into the control zone. Make access time limited and monitored, and remove old paths.
Find where IEC 60870-5-101/104, IEC 61850 or OPC traffic can be sent from a Windows host. Allow only expected sources and watch for new senders.
Check that configuration backups of RTUs, relays, engineering workstations and SCADA servers exist offline, and that restoring them has been tested.
Enable application whitelisting on static systems such as HMI and engineering workstations, as CISA advises.
Check that event logging cannot be turned off quietly on control-zone systems, and that alerts fire on new accounts, MS-SQL command use and odd file copies.
A modular malware framework built to affect industrial control systems in electrical substations. MITRE ATT&CK calls it the first publicly known malware specifically designed to affect the electric grid. CrashOverride is another name for it.
Just before midnight on 17 December 2016, according to the US Department of Energy laboratory report. Power was out for just over an hour.
The US Government attributes it to Russian nation-state cyber actors (CISA, 20 July 2021). MITRE ATT&CK and a US indictment tie it to Sandworm Team, the GRU unit 74455. The indictment contains charges, not a court verdict.
No. The 2015 attack used BlackEnergy and KillDisk against distribution companies. The 2016 attack used Industroyer and hit a transmission substation, per the sources opened. The indictment links both to the same unit.
CISA said in 2017 there was no evidence it had affected US critical infrastructure, but that the techniques could be changed to target US systems.
The US Department of Energy laboratory report names the Pivnichna transmission substation outside Kyiv. MITRE ATT&CK says distribution substations, so sources differ on the type.
Take control of your digital security with an exclusive demo of our AI-driven threat intelligence platform.