The DIVD CNA record says an authenticated attacker can read files from the underlying server through its XML interface. Information in those files could help an attacker compromise the system further.CISA added this identifier to its Known Exploited Vulnerabilities catalog on 25 November 2026. The catalog confirms exploitation but does not describe a victim, campaign or first exploitation date. Its federal remediation deadline is 28 November 2026; that date is not a general deadline for every organization.
What it allows
How Does CVE-2023-25914 Expose Controller Files?
The weakness is insufficient restriction of file paths handled by the XML interface. According to the DIVD CNA record, an authenticated attacker with network access could retrieve underlying server files. The record describes potential full system compromise as a consequence of information disclosure, not as automatic code execution by this flaw.
Authentication matters for exposure decisions: this is not described as an unauthenticated file read. A reachable management interface, an affected version and an account able to use the XML interface form the relevant conditions. Teams can use a vulnerability intelligence platform with their controller inventory to track this CVE and its KEV status.
CISA KEV confirms that CVE-2023-25914 has been exploited. The entry does not identify the intrusion path or say which files were accessed. The related Danfoss KEV news report covers several identifiers; this profile addresses the XML file reading flaw alone.
Who is affected
Which AK-SM800A Versions Are Affected?
The DIVD CNA record lists Danfoss AK-SM800A versions before 3.3 as affected and recommends updating to version 3.3. It does not supply a released lower version bound or a branch-by-branch table. Record the running software version for each controller and compare it with that threshold.
NVD's configuration lists firmware through 3.3, which conflicts with the CNA's affected interval and patch instruction. Treat 3.3 as the CNA's stated fix, and confirm the exact firmware applicability with Danfoss when an installation or version string is ambiguous. This difference is why a simple automated version range is omitted.
The CVE-2023-25915 command execution profile describes a separate flaw in this product family. Check its own affected versions and remediation guidance before treating one controller update as coverage for every identifier. Keep the patch management record for each device and its post-update version.
Timeline
- 2023-08-21
DIVD published the CVE record describing authenticated file reading through the AK-SM800A XML interface.
- 2026-11-25
CISA added CVE-2023-25914 to its Known Exploited Vulnerabilities catalog.
- 2026-11-28
CISA's remediation due date for covered federal agencies.
What to do
-
Inventory affected controllers
List AK-SM800A devices, their running versions, owners and management reachability. Prioritize versions before 3.3 with management access beyond intended administrators.
-
Apply the DIVD-listed update
Follow the Danfoss update procedure and move affected AK-SM800A devices to version 3.3 or a later applicable release. Confirm unusual firmware labels with Danfoss support.
-
Verify the running version
Read the version from each controller after maintenance and retain the result with its change record. Do not assume a downloaded package proves the running device was updated.
-
Review access to the management interface
Limit XML management access to intended administrators and review available access logs for unexpected authenticated activity. This is defensive guidance, not a published detection signature.
What Brandefense can do
- Watch your stack for exploited flaws
Name the vendors and products you run, and Brandefense alerts you when a CVE in them is exploited.
- See CVE-2023-25914 in Brandefense Atlas
The Atlas record of CVE-2023-25914: severity, exploitation status and the sources behind it.
- Vulnerability intelligence platform
Brandefense Vulnerability Intelligence follows which vulnerabilities attackers are using, so your team can patch what is under attack first.
Frequently Asked Questions
Does CVE-2023-25914 require authentication?
Yes. The DIVD CNA record describes authenticated attackers reading underlying server files through the XML interface.
Is CVE-2023-25914 in CISA KEV?
Yes. CISA added it on 25 November 2026, confirming known exploitation. The entry does not identify a specific victim or campaign.
Which version fixes the XML file reading flaw?
DIVD lists versions before 3.3 as affected and recommends version 3.3. Verify the running version after the update and confirm ambiguous firmware labels with Danfoss.
Is this the same as CVE-2023-25915?
No. CVE-2023-25914 concerns authenticated XML file reading. CVE-2023-25915 is a separate command execution record with its own assessment.
Sources
- CVE-2023-25914 RecordDIVD CNA via CVE Program
- Path Traversal in Danfoss AK-SM800ADIVD CSIRT
- Known Exploited Vulnerabilities CatalogCISA
- NVD CVE-2023-25914 RecordNIST NVD