Skip to content
NewCybercrime Report 2026 · Eight Chapters · A Post Is Not An Incident → Explore The ChaptersCybercrime Report 2026 → Explore

Danfoss AK-SM 800A Command Execution (CVE-2023-25915)

CVE-2023-25915 is an improper input validation flaw in the Danfoss AK-SM 800A Series.

Reviewed by
Brandefense Analyst Team
Published
Reading Time
3 min read
CVE ID
CVE-2023-25915
Vendor
Danfoss
Affected Product
AK-SM 800A Series
Exploitation
Listed in CISA KEV
Published
2023-08-19

DIVD says a remote attacker could execute arbitrary commands on an affected system. Its CVSS 3.1 vector indicates low privileges are required.The issue returned to operational priority when CISA added it to the Known Exploited Vulnerabilities catalog on 25 November 2026. DIVD recommends upgrading to package 3.3; Danfoss’s 2023 release describes package 3.3 as a security update. The original disclosure and the KEV addition are separate events.

What it allows

How Does CVE-2023-25915 Allow Command Execution?

DIVD identifies improper input validation as the cause. Danfoss describes security changes to authorization on XML requests in its software 3.3 release. Our reading places the risk in the controller’s remote management path. Improper input validation could lead to command execution on the affected system.

DIVD’s CVSS vector marks network access, low attack complexity and low privileges. Successful exploitation could affect confidentiality, integrity and availability on the controller. That score does not identify the attacker or explain how access was obtained.

Why Does the CISA KEV Listing Change Priority?

CISA listed this specific CVE on 25 November 2026, more than three years after the initial disclosure. Its catalog treats the flaw as known exploited and gives 28 November 2026 as the federal remediation deadline. CISA lists ransomware campaign use as unknown.

The KEV entry supports urgent review of unpatched AK-SM 800A deployments. It does not identify which individual devices were targeted. Use Vulnerability Intelligence alongside your asset inventory to prioritize confirmed exposures.

CISA also listed CVE-2023-25914, a path traversal issue, and CVE-2025-41450, an authentication issue. They are separate records with different effects. The Danfoss KEV news report covers the catalog change across those records.

Who is affected

Which AK-SM 800A Versions Need the Fix?

DIVD identifies Danfoss AK-SM 800A software before 3.3 as affected and directs operators to upgrade to 3.3. Danfoss calls package 3.3 a security update and says it requires Danux 4.14.13.194 or later. Check both the appliance model and the running software before deciding its status.

NVD’s configuration data lists firmware through 3.3, which conflicts with DIVD’s fix statement and Danfoss’s release note. This profile follows DIVD’s 3.3 fix guidance and Danfoss’s 3.3 security release while flagging the discrepancy for manual verification. If the device reports an ambiguous build, confirm its update status with Danfoss support.

Danfoss lists AK-SM 820A, 850A and 880A variants in the 3.3 release. The release also notes that XML header authentication is disabled by default to preserve existing integrations. Review remote access and integration settings during the patch management process.

Timeline

  1. 2023-08-19

    DIVD published the CVE record and recommended software package 3.3.

  2. 2026-11-25

    CISA added CVE-2023-25915 to its Known Exploited Vulnerabilities catalog.

What to do

  1. Find affected controllers

    Inventory AK-SM 800A units, including 820A, 850A and 880A variants. Record the installed software, running build, Danux version and remote management exposure.

  2. Limit management reachability

    Restrict unnecessary access to the management interface while the update is scheduled. Review XML integration permissions and authentication settings without assuming a setting alone fixes this CVE.

  3. Prepare and install package 3.3

    Follow Danfoss’s update sequence. Back up the unit, check alarms and manual overrides, update Danux to at least 4.14.13.194, then install software package 3.3 or a later fixed release.

  4. Verify the operating build

    After maintenance, confirm that the controller runs package 3.3 or a later fixed release. Check normal operation, XML integrations and retained update records.

  5. Review suspicious activity

    As a defensive recommendation, examine available management activity and configuration changes on previously exposed units. Escalate unexplained changes through the incident process.

What Brandefense can do

Frequently Asked Questions

Does CVE-2023-25915 require an authenticated attacker?

DIVD’s CVSS 3.1 vector includes PR:L, which means low privileges are required in that scoring scenario. It also rates attack complexity as low.

Which Danfoss software package addresses CVE-2023-25915?

DIVD identifies package 3.3 as the CVE fix; Danfoss describes package 3.3 as a security update. Danfoss says Danux 4.14.13.194 or later is a prerequisite.

Why do the affected-version records disagree?

DIVD identifies 3.3 as the fix, and Danfoss describes it as a security update; NVD configuration data includes version 3.3. Verify the installed build and consult Danfoss if its status is unclear.

Sources

  1. Remote Command Execution in Danfoss AK-SM800ADIVD CSIRT
  2. AK-SM 800A Software Release 3.3Danfoss
  3. CVE-2023-25915 NVD RecordNVD
  4. Known Exploited Vulnerabilities CatalogCISA
ShareLinkedInX